Solar Energy

Location | MONTHS (KCal/m2 - Day) |
|||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
|
ADANA | 1257 |
1970 |
2850 |
3616 |
4462 |
4658 |
4326 |
4238 |
3566 |
2634 |
1625 |
1258 |
ANTALYA | 1554 |
1977 |
2868 |
3915 |
4386 |
4928 |
4994 |
4748 |
3740 |
2712 |
1907 |
1227 |
G. ANTEP | 1479 |
2202 |
3023 |
4222 |
4378 |
5414 |
5280 |
5036 |
4013 |
2795 |
1894 |
1368 |
Sukal Solar Energy Calculations
Daily Water Requirement
Daily hot water consumption has been regarded as 50 liters/day.
V = (No. of Consumer) x 50 liters/day. (It has been supposed that 4 people live in each house.)
Water’s Temperature of for Solar Collector Inlet
Temperature of the cold water going into the installation should be supposed 2-300C lower than the fresh air outdoor.
Temperature of Potable Water

Potable water is supposed 40-600for usage purposes. Daily heat requirement for providing hot water (Q) is:

No. of collectors after required daily energy amount (Q) is found:
Example: Let’s find out how many collectors are necessary in order to meet
a 10-family flat’s hot water requirement: (Let’s make the calculations according to September.)
Daily hot water requirement; V = 10 x 4 x 50 V = 2000 liters/day
Required energy; Q = 60.000 KCal/day



SUKAL Solar Collector Sizes

150 liter capacity hot water tank,
500 liters cold water tank having base made of profile, optimum and easy mounting.